Coding in the delivered condition
Possible change
Mixer circuit
F2:8
*
1
Time limit for party
mode 8 hours or exter-
nal operating mode
changeover via key
*
2
F2:0
No time limit for party
mode
F2:1
to
F2:12
Time limit adjustable from
1 to 12 hours
*
2
F5:12
Run-on time of the inter-
nal circulation pump in
heating mode 12 min
F5:0
No run-on time of the in-
ternal circulation pump
F5:1
to
F5:20
Run-on time of the inter-
nal circulation pump ad-
justable from 1 to 20 min
F6:25
*
3
The internal circula-
tion pump is perma-
nently ON in the "DHW
only" operating mode
F6:0
In the "DHW only" operat-
ing mode, the internal cir-
culation pump is
permanently OFF
F6:1
to
F6:24
In the operating mode
"DHW only", the internal
circulation pump will be
started 1 to 24 times per
day for 10 min respec-
tively
F7:25
*
3
Internal circulation
pump is permanently
ON in "Standby mode".
F7:0
*
3
Internal circulation
pump is permanently
OFF in "Standby mode"
F7:1
to
F7:24
In operating mode
"Standby mode", the in-
ternal circulation pump
will be started 1 to 24
times per day for 10 min
respectively
Resetting codes to the delivered condition
1.
Press
L
and
G
simultaneously
for approx. 2 s.
Code 2
(cont.)
61
Coding
5692
569
GB
*1
Only for weather-compensated control units.
*2
Party mode ends
automatically
in heating program "
rw
" when the system changes
over to operation with standard room temperature.
*3
Only for constant temperature control units.
Summary of Contents for Vitodens 300
Page 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Page 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Page 127: ...127 5692 569 GB...