Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A6:36
*
1
Extended economy
mode
disabled
A6:5
to
A6:35
Extended economy mode
is enabled, i.e. the burner
and heating circuit pump
will be switched OFF and
the mixer will be closed at
a variable value, which is
adjustable between 5 and
35 °C plus 1 °C. This
value is based on the ad-
justed outside tempera-
ture, comprising the
actual outside tempera-
ture and a time constant,
which takes the cooling
down of an average
building into considera-
tion.
A7:0
*
1
Without mixer econo-
my function
A7:1
With mixer economy
function (extended heat-
ing circuit pump logic):
Heating circuit pump also
OFF, if the mixer was
moved to the closed posi-
tion for longer than
20 min. Heating pump
ON,
&
if the mixer changes to
control mode
or
&
after cylinder heating
(for 20 min)
or
&
if there is a risk of frost.
A8:1
*
1
Heating circuit M2
(mixer circuit) creates a
demand for the internal
circulation pump
A8:0
Heating circuit M2 (mixer
circuit) creates no de-
mand for the internal cir-
culation pump
Code 2
(cont.)
55
Coding
5692
569
GB
*1
Only for weather-compensated control units.
Summary of Contents for Vitodens 300
Page 111: ...Parts lists cont 111 Parts lists 5692 569 GB...
Page 112: ...Parts lists cont 112 Parts lists 5692 569 GB...
Page 113: ...Parts lists cont 113 Parts lists 5692 569 GB...
Page 114: ...Parts lists cont 114 Parts lists 5692 569 GB...
Page 115: ...Parts lists cont 115 Parts lists 5692 569 GB...
Page 127: ...127 5692 569 GB...