Checking and adjusting the ignition and ionisation electro-
des
A
Ignition electrodes
B
Ionisation electrode
1.
Check the electrodes for wear and
contamination.
2.
Clean the electrodes with a small
brush (not with a wire brush) or
emery paper.
!
Please note
Never damage the wire
gauze.
3.
Check clearances. If the gaps are
not as specified or the electrodes
are damaged, replace and align the
electrodes together with new gas-
ket
A
. Tighten the electrode fixing
screws with 2 Nm.
Further details regarding the individual steps
(cont.)
20
Initial start-up, inspection, maintenance