32
Recommended flexible power cables
Indoor unit
Power supply
Cable
Max. cable length
Heat pump control unit
230 V~
■
Without power-OFF
3 x 1.5 mm
2
■
With power-OFF
5 x 1.5 mm
2
Instantaneous heating water
heater
■
400 V~
5 x 2.5 mm
2
25 m
■
230 V~
7 x 2.5 mm
2
25 m
Outdoor units
Heat pumps with outdoor unit 230 V
Types
Cable
Max. cable length
Max. fuse rating
201.A04
3 x 2.5 mm
2
29 m
B16A
201.A06
3 x 2.5 mm
2
29 m
B16A
201.A08
3 x 2.5 mm
2
29 m
B16A
201.A10
3 x 2.5 mm
2
20 m
B25A
Or
3 x 4.0 mm
2
32 m
201.A13
3 x 2.5 mm
2
20 m
B25A
Or
3 x 4.0 mm
2
32 m
201.A16
3 x 2.5 mm
2
20 m
B25A
Or
3 x 4.0 mm
2
32 m
Heat pumps with outdoor unit 400 V
Types
Cable
Max. cable length
Max. fuse rating
201.A10
5 x 2.5 mm
2
30 m
B16A
201.A13
5 x 2.5 mm
2
30 m
B16A
201.A16
5 x 2.5 mm
2
30 m
B16A
Installation sequence
Electrical connection
(cont.)
6150148
Installation