54
Types
Cable
Max. cable length
Max. fuse rating
201.A04
3 x 2.5 mm
2
29 m
B16A
201.A06
3 x 2.5 mm
2
29 m
B16A
201.A08
3 x 2.5 mm
2
29 m
B16A
201.A10
3 x 2.5 mm
2
20 m
B25A
Or
3 x 4.0 mm
2
32 m
201.A13
3 x 2.5 mm
2
20 m
B25A
Or
3 x 4.0 mm
2
32 m
201.A16
3 x 2.5 mm
2
20 m
B25A
Or
3 x 4.0 mm
2
32 m
Outdoor unit power supply 400 V~
!
Please note
Incorrect phase sequence can cause damage to
the appliance.
Make the compressor power supply
only
in the
phase sequence specified (see terminals) with a
clockwise
rotating field.
L1
L2
L3
N
GND Rx/Tx-Rx/Tx+
Modbus
B
A
L1
L2
L3
N
PE
PE
B
C
Fig. 50
A
Outdoor unit wiring chamber: See "Opening the
outdoor unit wiring chamber".
B
Power supply 400 V/50 Hz
C
Separator (supplied)
Danger
Serious injury can be caused by electric current
and appliance damage can result if wires drift
into the adjacent voltage area.
It is essential to insert the separator supplied.
Installation sequence
Power supply
(cont.)
6150148
Installation