95
Electric booster heater
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Enable instantaneous heating water
heater"
7900
1
"Enable electric heaters for DHW heat-
ing"
7901
0
"Enable instant. heating water heater for
central heating"
7902
0
"Start delay instantaneous heating water
heater"
7905
30 min
"Max. output instantaneous heating wa-
ter heater"
7907
3
"Output for instant. heating water heater
at power-OFF"
790A
0
"Dual mode temp. instant. heating water
heater"
790B
500 (
≙
50 °C)
Internal hydraulics
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
Heat pump for drying a building
7300
0
Time program for screed drying
7303
0
Set flow temperature external demand
730C
500 (
≙
50 °C)
Start threshold
730E
300 (
≙
30 K
·
min)
Compressor performance at min. outside
temperature
730F
50 %
Compressor performance at max. outside
temperature
7310
20 %
Cooling start threshold
7311
100 (
≙
10 K
·
min)
Elec. heater start threshold
7312
300 (
≙
30 K
·
min)
Cycle rate heating circuit pumps
7319
0
Secondary circuit pump type
735A
0
Starting time high efficiency circulation
pump
7365
Do not adjust.
Screed program start day
7378
1
Screed program end day
7379
31
Primary source
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
"Primary source ctrl strategy"
7401
Never adjust
Commissioning/service reports
Control parameter report
(cont.)
6150148
Appendix