106
Type AWO-M/AWO-M-E/AWO-M-E-AC
201.A04
201.A06
201.A08
201.A10
201.A13
201.A16
Connections
(female thread)
Heating water flow
G
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Heating water return and DHW
cylinder return
G
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
DHW cylinder flow
G
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Secondary circuit flow
G
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Secondary circuit return
G
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Length of connection line be-
tween indoor
—
outdoor units
(Hydraulic connection set)
m
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
1 to 20
Sound power of outdoor unit
at rated
heating output
(Measurements with reference to EN 12102/
EN ISO 9614-2)
Weighted total sound power level
■
At A7
±
3 K
/W55
±
5 K
(max.)
dB(A)
56
56
58
60
61
61
■
At A7
±
3 K
/W55
±
5 K
in night mode dB(A)
50
50
50
55
55
55
Energy efficiency class
to EU
Regulation no. 813/2013
Heating, average climatic condi-
tions
■
Low temperature applications
(W35)
A
++
A
++
A
+++
A
+++
A
+++
A
+++
■
Medium temperature applica-
tions (W55)
A
+
A
++
A
++
A
++
A
++
A
++
Performance data
as per EU
Regulation no. 813/2013 (aver-
age climatic conditions)
Low temperature applications
(W35)
■
Energy efficiency
η
S
%
173
172
175
176
175
175
■
Rated heating output P
rated
kW
5.38
5.59
6.82
9.32
9.99
10.61
■
Seasonal coefficient of per-
formance (SCOP)
4.40
4.38
4.46
4.47
4.46
4.46
Medium temperature applica-
tions (W55)
■
Energy efficiency
η
S
%
124
125
127
129
130
130
■
Rated heating output P
rated
kW
5.23
5.59
6.41
9.35
10.07
10.72
■
Seasonal coefficient of per-
formance (SCOP)
3.18
3.21
3.25
3.29
3.32
3.34
Sound power level to ErP
Sound power level, outdoor unit
dB(A)
53
54
55
56
56
56
Specification
Specification
(cont.)
6150148
Appendix