108
Type AWO/AWO-E/AWO-E-AC
201.A10
201.A13
201.A16
Outdoor unit electrical values
Rated voltage, compressor
3/N/PE 400 V/50 Hz
Max. operating current, compressor
A
8.7
8.7
8.7
Cos
φ
0.96
0.96
0.96
Starting current, compressor
A
15
15
15
Fuse rating
B16A
B16A
B16A
IP rating
IPX4
IPX4
IPX4
Indoor unit electrical values
Heat pump control unit/PCB
■
Rated voltage, control unit/PCB
1/N/PE 230 V/50 Hz
■
Power supply fuse rating
1 x B16A
1 x B16A
1 x B16A
■
Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water heater
■
Type AWO-E/AWO-E-AC:
Factory-fitted
■
Type AWO:
Accessories
■
Rated voltage
1/N/PE 230 V/50 Hz
or
3/N/PE 400 V/50 Hz
■
Heating output
kW
9
9
9
■
Power supply fuse rating
3 x B16A
3 x B16A
3 x B16A
Max. power consumption
Fan
W
2 x 45
2 x 45
2 x 45
Outdoor unit
kW
5.13
5.13
5.15
Secondary pump (PWM)
W
60
60
60
■
Energy efficiency index EEI
≤
0.2
≤
0.2
≤
0.2
Control unit/PCB, outdoor unit
W
15
15
15
Control unit/PCB, indoor unit
W
10
10
10
Control unit/PCB power, indoor unit
W
1000
1000
1000
Refrigerant circuit
Refrigerant
R410A
R410A
R410A
■
Safety assembly
A1
A1
A1
■
Refrigerant charge
kg
2.40
2.40
2.40
■
Global warming potential (GWP)
*3
1924
1924
1924
■
CO
2
equivalent
t
4.6
4.6
4.6
Compressor (hermetically sealed)
Type
Scroll
Scroll
Scroll
■
Oil in compressor
Type
3 MAF POE
3 MAF POE
3 MAF POE
■
Quantity of oil in compressor
l
1.17
1.17
1.17
Permissible operating pressure
■
High pressure side
bar
43
43
43
MPa
4.3
4.3
4.3
■
Low pressure side
bar
28
28
28
MPa
2.8
2.8
2.8
*3
Based on the Fifth Assessment Report of the Intergovernmental Panel on Climate Change (IPCC)
Specification
Specification
(cont.)
6150148
Appendix