101
Photovoltaics
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
Enable own energy consumption PV
7E00
0
Prop. of external current
7E02
10 (
≙
10 %)
Threshold for electrical power
7E04
0 (
≙
0 W)
Stop threshold (relative)
7E07
0 (
≙
0 kW)
Enable own energy consumptn for set DHW
temperature 2
7E10
0
Enable own energy consumption for DHW
heating
7E11
0
Enable own energy consumptn for heating
water buffer cyl.
7E12
0
Enable own energy consumption for heating 7E13
0
Enable own energy consumption for cooling 7E15
0
Enable own energy consumptn for coolant
buffer cylinder
7E16
0
Raise set DHW cylinder temperature PV
7E21
0 (
≙
0 K)
Raise set heating water buffer cylinder temp
PV
7E22
0 (
≙
0 K)
Raise set room temperature PV
7E23
0 (
≙
0 K)
Reduce set room temperature PV
7E25
0 (
≙
0 K)
Reduce set coolant buffer cylinder tempera-
ture PV
7E26
0
Smart Grid
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Enable Smart Grid"
7E80
0
"Smart Grid Enable elec heat"
7E82
0
"Smart Grid set value increase for DHW
heating"
7E91
0 (
≙
0 K)
"Smart Grid set value increase for htg
wtr buff"
7E92
0 (
≙
0 K)
"Smart Grid set value increase for centr
htg"
7E93
0 (
≙
0 K)
"Smart Grid set value decrease for room
t cool"
7E95
0 (
≙
0 K)
Time
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Automatic changeover summertime -
wintertime"
7C00
1
"Start summertime - month"
7C01
3
"Start summertime - week"
7C02
5
"Start summertime - day"
7C03
7
"Start wintertime - month"
7C04
10
"Start wintertime - week"
7C05
5
"Start wintertime - day"
7C06
7
Commissioning/service reports
Control parameter report
(cont.)
6150148
Appendix