Parameters for swimming pool water heating
Parameter
Setting
"System definition"
Ó
"External extension 7010"
"1"
or
"3"
"Swimming pool 7008"
"1"
Parameters for ventilation with Vitovent 200-C
Parameter
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"2"
Vitovent 200-C
Further enabling for Vitovent 200-C if necessary
Parameter
Setting
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"0"
Defrosting without preheating coil
(
"Strategy, passive frost pro-
tection 7D2C"
)
"1"
Frost protection with preheating
coil; defrosting via bypass
"2"
Frost protection with preheating
coil; comfort function
"Strategy, passive frost protection 7D2C"
"0"
Fans OFF
"1"
Defrosting via bypass
"2"
Supply air fan OFF
"Type of heat exchanger 7D2E"
"0"
Countercurrent heat exchanger
"1"
Enthalpy heat exchanger
"Installation position 7D2F"
"0"
Ceiling mounting
"1"
Wall mounting
"Function, external 230 V input, ventilation 7D3A"
"1"
External switch (bathroom switch)
enabled
Adjust values for Vitovent 200-C if necessary
Parameter
Setting
"Ventilation"
Ó
"Set room temperature 7D08"
"100"
to
"300"
(
≙
10 to 30 °C)
"Flow rate reduced ventilation 7D0A"
Subject to sizing
Ventilation unit service instruc-
tions
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Parameters for ventilation with Vitovent 200-W/300-C/300-W
Parameter
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"3"
Vitovent 200-W
or
Vitovent 300-C
or
Vitovent 300-W
Commissioning, inspection, maintenance
Commissioning the system
(cont.)