Initial start−up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Checking and adjusting the ignition and ionisation electrodes
A
Ignition electrodes
B
Ionisation electrode
1.
Check the electrodes for wear and
contamination.
2.
Clean the electrodes with a small
brush or emery paper.
¨
Ensure that the wire mesh is
not damaged.
3.
Check all clearances. If the gaps
are not as specified or the
electrodes are damaged, replace
and align the electrodes together
with new gaskets.
Tighten the fixing screws with
2Nm.
Disconnecting the neutralising system
(if installed)
,
and connecting a drain hose
1.
Separate the hose to the
neutralising system from
siphon
A
.
2.
Connect drain hose to siphon
A
and to a sewer.