53
Appendix
Specification
(cont.)
MatriX radiant burner specification
Rated output range
of the boiler
kW
9
27
12
35
16
49
22
66
Burner type
VGMI1
VGMI2
VGMI3 VGMI4
Voltage
V
230
230
230
230
Frequency
Hz
50
50
50
50
Power consumption
W
45
49
74
102
Fan speed at rated output
min
1
4
256
4
480
5
056
5
952
Gas throughput subject to the operational net calorific value (H
uB
)
Natural Net calorific
Rated boiler output
gas
group
value
H
uB
27kW
35kW
49kW
66 kW
kWh/m
3
MJ/m
3
m
3
/h l/min m
3
/h l/min m
3
/h l/min m
3
/h l/min
E
9.45
34.02
2.6
43.3
3.5
60.0
4.8
85.0
6.6 110.0
LL
8.13
29.25
3.1
51.6
4.1
70.0
5.6
98.3
7.7 128.0