21
Initial start−up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Checking the condensate drain and the neutralising system
(if
installed)
for continuity and leaks
Check the condensate drain system
for leaks.
To do this, fill the open combustion
chamber with water.
Water must be able to flow without
backpressure via the condensate
drain system.
Otherwise, clean the complete
condensate drain system again.
¨
Observe the neutralising system
manufacturer’s instructions.
Checking gaskets, packing cords and thermal insulation
1.
Check gaskets and packing cords.
2.
Check the thermal insulation of the
burner.
3.
Replace all faulty parts.
4.
Check the thermal insulation of the
boiler for good fit and adjust if
required.
5692500GB