17
Initial start−up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Checking burner gauze assembly
Replace the burner gauze assembly if
the wire mesh is damaged.
1.
Remove ignition and ionisation
electrodes
A
.
2.
Turn thermal insulation ring
B
clockwise and remove carefully.
3.
Slacken eight Torx screws
C
, and
remove burner gauze assembly
D
and assembly gasket
E
.
4.
Insert a new burner gauze
assembly
D
with new assembly
gasket
E
, and secure with eight
Torx screws.
Torque: 4.5Nm
5.
Refit thermal insulation ring
B
and ignition and ionisation
electrodes
A
.
5692500GB
B A
C
A
D
E
Summary of Contents for CU3