26
Troubleshooting
Selecting manual mode
Manual mode and service display
A heat demand from the control unit must be present to call up the service
display and for manual mode.
In the service display, the current level of modulation is shown in %.
Whereby:
"
d00
" represents the lower rated output
and
"
d00
." (with a decimal point behind the last figure) represents the upper
rated output.
1.
Press keys
b
and
S
simultaneously; the burner
changes over into manual mode.
Below status, the display shows
"
d
".
2.
Set the lower rated output:
Press key
b
, until the display
shows "
d00
".
3.
Set the upper rated output:
Press key
a
, until the display
shows "
d00
.".
4.
Press keys
b
and
S
simultaneously;
the burner will return to
modulating mode.
5692500GB
Status
Service