110
Coding in the delivered condition
Possible change
0E:1
Solar yield calculated in
conjunction with
Viessmann heat transfer
medium.
0E:2
Solar yield calculated in
conjunction with water as
heat transfer medium. Do
not adjust
0E:0
No heat statement
0F:70
The flow rate of the solar
circuit at the maximum
pump speed is set to
7 l/min.
0F:1
to
0F:255
Flow rate adjustable from
0.1 to 25.5 l/min.
1 step
≙
0.1 l/min.
10:0
Target temperature con-
trol switched off (coding
address "11").
10:1
Target temperature control
switched on
11:50
Target temperature con-
trol switched on (code
"10:1"):
Set solar cylinder temper-
ature 50 °C.
Temperature at which the
solar heated water is to
be stratified into the DHW
cylinder.
11:10
to
11:90
Set cylinder temperature
adjustable from 10 to
90 °C.
12:10
Minimum collector tem-
perature (minimum start
temperature for the solar
circuit pump) 10 °C.
12:0
Minimum limit disabled
12:1
to
12:90
Minimum collector temper-
ature adjustable from 1 to
90 °C.
"Heating circuit ..."
Select group
"Heating circuit ..."
(see
page 97).
Coding
Coding in the delivered condition
Possible change
A0:0
Without remote control
A0:1
With Vitotrol 200A/200 RF
(automatic recognition)
A0:2
With Vitotrol 300A/300 RF
or Vitocomfort (automatic
recognition)
Code 2
"Solar"
(cont.)
5773 238 GB
Summary of Contents for B2UA
Page 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Page 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Page 199: ...199 5773 238 GB ...