88
Coding in the delivered condition
Possible change
Lock out controls
8F:0
Operation enabled in
standard menu and ex-
tended menu.
Note
The respective code is
only activated when you
exit the service menu.
8F:1
Operation blocked in
standard menu
and
exten-
ded menu.
Emissions test mode can
be enabled.
8F:2
Operation enabled in
standard menu and
blocked in extended
menu.
Emissions test mode can
be enabled.
Set flow temperature for external demand
9b:70
Set flow temperature for
external demand 70 °C
9b:0
to
9b:127
Set value adjustable from 0
to 127 °C (limited by boiler-
specific parameters)
"Boiler"
Select group
"Boiler"
(see page 85).
Coding
Coding in the delivered condition
Possible change
Burner service in 100 hours
21:0
No service interval (hours
run) selected
21:1
to
21:100
The number of hours run
before the burner should
be serviced is adjustable
from 100 to 10 000 h.
One adjusting step
≙
100 h
Service interval in months
23:0
No interval for burner
service
23:1
to
23:24
Interval adjustable from 1
to 24 months
Code 1
"General"
(cont.)
5773 238 GB
Summary of Contents for B2UA
Page 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Page 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Page 199: ...199 5773 238 GB ...