57
Yes
Automatic calibra-
tion of the com-
bustion controller
No
Fault E3
Ensure adequate
heat transfer.
Press reset button
R
.
Fault Eb
Check gap be-
tween ionisation
electrode and
burner gauze as-
sembly.
Check allocation of
gas type (coding
address 82, gas
train setting).
Check flue system;
remedy flue gas re-
circulation if re-
quired.
Press reset button
R
.
For further details regarding faults, see
page 124.
Setting the max. heating output
The maximum output for
heating oper-
ation
can be limited. The limit is set via
the modulation range. The max. adjust-
able output is limited upwards by the
boiler coding card.
Service menu
1. Press
OK
and
å
simultaneously for
approx. 4 s.
2.
"Service functions"
3.
"Max. output"
4.
"Change?"
Select
"Yes"
.
A value is shown on the display (e.g.
"85"
). In the delivered condition, this
value represents 100 % of rated heat-
ing output.
5. Set the required value.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Service
Summary of Contents for B2UA
Page 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Page 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Page 199: ...199 5773 238 GB ...