127
Displayed
fault code
System characteris-
tics
Cause
Measures
94
No solar DHW heat-
ing.
Short circuit, cylin-
der temperature
sensor; tempera-
ture sensor
%
connection on the
solar control mod-
ule.
Check cylinder tempera-
ture sensor (see
page 140)
9A
No solar DHW heat-
ing.
Lead break, collec-
tor temperature
sensor; tempera-
ture sensor
&
connection on the
solar control mod-
ule.
Check collector tempera-
ture sensor (see
page 140)
9C
No solar DHW heat-
ing.
Lead break, cylin-
der temperature
sensor; tempera-
ture sensor
%
connection on the
solar control mod-
ule.
Check cylinder tempera-
ture sensor (see
page 140)
9E
Control mode
No flow rate in so-
lar circuit or flow
rate too low, or
temperature limiter
has responded.
Check solar circuit.
Acknowledge fault mes-
sage (see separate instal-
lation and service instruc-
tions).
9F
Control mode
Solar control mod-
ule fault
Replace solar control
module
A2
Emergency mode
where system pres-
sure is too low
System pressure
too low
Top up with water
Troubleshooting
Fault codes
(cont.)
5773 238 GB
Service
Summary of Contents for B2UA
Page 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Page 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Page 199: ...199 5773 238 GB ...