82
All coding addresses in the table are listed in the "General" group.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
LON
LON
LON
Subscriber no. 1,
Code "77:1".
Subscriber no. 10,
Code "77:10".
Subscriber no. 11,
Set
code "77:11".
Subscriber
no. 99.
Control unit is fault
manager,
Code "79:1".
Control unit is not
fault manager,
Code "79:0".
Control unit is not
fault manager,
Code "79:0".
Device is fault
manager.
Control unit transmits
the time,
Code "7b:1".
Control unit receives
the time,
Set
code "81:3".
Control unit receives
the time,
Set
code "81:3".
Device re-
ceives the
time.
Control unit transmits
outside temperature,
Set
code "97:2".
Control unit receives
outside tempera-
ture,
Set
code "97:1".
Control unit receives
outside tempera-
ture,
Set
code "97:1".
—
Viessmann system
number,
Code "98:1".
Viessmann system
number,
Code "98:1".
Viessmann system
number,
Code "98:1".
—
LON subscriber fault
monitoring,
Code "9C:20".
LON subscriber fault
monitoring,
Code "9C:20".
LON subscriber fault
monitoring,
Code "9C:20".
—
Carrying out a LON subscriber check
The subscriber check is used to test
communication with the system devices
connected to the fault manager.
Preconditions:
■ The control unit must be programmed
as
fault manager
(code "79:1" in the
"General"
group).
■ The LON subscriber number must be
programmed in all control units.
■ The LON subscriber list in the fault
manager must be up to date.
Service menu:
1. Press
OK
and
simultaneously for
approx. 4 s.
2.
"Service functions"
3.
"Subscriber check"
4. Select subscriber (e.g. subscriber 10).
5. Start the subscriber check with
"OK"
.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 238 GB
Summary of Contents for B2UA
Page 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Page 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...