Coding in the delivered condition
Possible change
Heating mode/reduced
mode: Weather-compen-
sated
b0:2
Heating mode: With room
temperature hook-up
Reduced mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b2:8
Only for heating circuit
with mixer and remote
control, and operation
with room temperature
hook-up must be pro-
grammed for the heating
circuit:
Room influence factor 8
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor ad-
justable from 1 to 64. The
higher the value, the great-
er the room influence.
b5:0
Only for heating circuit
with mixer and remote
control:
Without room tempera-
ture-dependent heating
circuit pump logic func-
tion
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table.
Parameter ad-
dress b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
> RT
set
RT
actual
< RT
set
– 1 K
7
RT
actual
> RT
set
– 1 K
RT
actual
< RT
set
– 2 K
8
RT
actual
> RT
set
– 2 K
RT
actual
< RT
set
– 3 K
Coding in the delivered condition
Possible change
C5:20
Electronic minimum flow
temperature limit 20 °C
(only in operation with
standard room tempera-
ture)
C5:1
to
Minimum limit adjustable
from 1 to 127 °C (limited by
boiler-specific parameters)
Code 2
"Heating circuit ..."
(cont.)
5773 238 GB
Summary of Contents for B2UA
Page 10: ...10 13 14 15 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 11: ...11 16 Preparing for installation Preparing the installation cont 5773 238 GB Installation ...
Page 12: ...12 sF 17 19 21 20 18 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 14: ...14 27 26 25 Preparing for installation Preparing the installation cont 5773 238 GB ...
Page 41: ...41 2x 1 4 2 3 5 Installation sequence Fitting the front panels 5773 238 GB Installation ...
Page 199: ...199 5773 238 GB ...