Outdoor unit power supply 230 V~
Type AWT/AWT-AC
221.A04
221.A05/A07
221.A10/A13
?
C N L
?
B
L1
N
A
Fig. 39
COM
Ni
?
Li
N
0
L
0
B
?
N L1
A
?
Fig. 40
?
N L
?
N L
C2 C1
B
?
N L1
A
Fig. 41
A
Outdoor unit wiring chamber: see page 40.
B
Power supply 230 V/50 Hz
Type AWT/AWT-AC
221.A04
221.A05
221.A07
221.A10
221.A13
Cable cross-section
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 4.0 mm
2
Max. cable length
29 m
25 m
25 m
20 m
20 m
or
or
Cable cross-section
—
—
—
3 x 4.0 mm
2
3 x 6.0 mm
2
Max. cable length
—
—
—
32 m
30 m
Fuse protection
B20A
B20A
B20A
B20A
B32A
Outdoor unit power supply 400 V~
!
Please note
Incorrect phase sequence can cause damage to
the appliance.
Make the compressor power supply
only
in the
phase sequence specified (see terminals) with a
clockwise
rotating field.
Type AWT/AWT-AC 221.B10/B13/B16
?
N L
?
N L3
C2 C1
B
?
N
L1
A
L2L1
L2
L3
Fig. 42
A
Outdoor unit wiring chamber: see page 40.
B
Power supply 400 V/50 Hz
Type AWT/AWT-AC
221.B10
221.B13
221.B16
Cable cross-section
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
Max. cable length
30 m
30 m
30 m
Fuse protection
B16A
B16A
B16A
Installation sequence
Power supply
(cont.)
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...