58
Checking electrical connections of the outdoor unit for firm seating
Danger
Contact with 'live' components can lead to seri-
ous injury from electric current. Some compo-
nents on PCBs remain 'live' even after the
power supply has been switched off.
■
When working on the external unit, isolate the
system from the power supply, e.g. at a sepa-
rate MCB/fuse or a mains isolator. Check the
system is no longer 'live' and safeguard
against reconnection.
■
Prior to working on the appliance, wait at
least 4 min until the voltage has completely
dropped out.
Closing the heat pump
See page 48.
Switching on the power supply
Switch on the power supply at the main MCB/fuse.
Starting the heat pump
!
Please note
Operating the appliance with insufficient refriger-
ant results in appliance damage.
■
Before starting the appliance, the internal unit
and the refrigerant lines must be charged with
the indicated amount of refrigerant: See chap-
ter "Charging the refrigerant lines and internal
unit".
■
The refrigerant circuit must be checked for
tightness: See chapter "Checking the refriger-
ant circuit for tightness".
■
The fill valves on the external unit must be
open when the appliance is switched on: See
chapter "Charging the refrigerant lines and
internal unit".
Follow the sequence shown
1.
Switch ON external unit voltage.
2.
Wait 2 min.
3.
Switch ON internal unit voltage.
4.
Start internal unit at the ON/OFF switch.
Note
If the internal unit is switched on before the external
unit or the waiting time is shorter than 2 min, the fault
message
"0A Fault external unit"
appears.
"Vitotronic 200" service instructions
Commissioning, inspection, maintenance
Checking the thermal insulation of flared connections
5776 028 GB
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...