30
F
E
D
C
Fig. 23
Safety assembly supplied
C
Pressure gauge
D
Connection G
¾
E
Quick-action air vent valve
F
Safety valve
1.
Connect the secondary lines to the heat pump:
!
Please note
Mechanically loaded hydraulic connections
lead to leaks, vibration and appliance dam-
age.
Connect on-site lines so that they are free of
load and torque stress.
!
Please note
Leaking hydraulic connections lead to appli-
ance damage.
Ensure the diaphragm grommets at the pipe
entries are seated correctly. Seal pipe
entries with sealing tape if necessary.
See chapter "Assembly and sealing faces to note".
2.
Install the safety assembly provided: Either to an
on-site line in the heating water return or to the
secondary circuit connection set (accessories)
Connection set installation instructions
3.
!
Please note
Leaking hydraulic connections lead to appli-
ance damage.
■
Check tightness of the internal and on-site
hydraulic connections.
■
In the event of leaks, drain off liquid via the
drain valve. Check the seating of seal
rings.
Always
replace displaced seal
rings.
Observe additional information regarding filling and
venting: See chapter "Filling and venting the sec-
ondary side".
4.
Thermally insulate pipes inside the building.
Note
■
With underfloor heating circuits, install a temperature
limiter to restrict the maximum temperature of under-
floor heating systems: See chapter on connecting a
temperature limiter to restrict the maximum tempera-
ture in underfloor heating systems.
■
Ensure the minimum flow rate, e.g. by means of an
overflow valve: See "Specification".
■
The secondary circuit must be equipped on site with
an expansion vessel.
Installation sequence
Connecting the secondary circuit
(cont.)
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...