26
Tighten nuts with the following torque:
Type AWT/AWT-AC
Line
Connection to the
outdoor unit
Torque in Nm
221.A04
Liquid line
7
6 mm
⁷
⁄
₁₆
UNF
14 to 18
Hot gas line
7
12 mm
¾
UNF
50 to 62
221.A05
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
221.A07
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
221.A10
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
221.A13
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
221.B10
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
221.B13
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
221.B16
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
Connection to indoor unit
Note
For connecting the refrigerant lines, we recommend
the use of either the pipe bends supplied or the refrig-
erant lines connection set (accessories). Depending on
the installation conditions, it may also be possible to
connect the refrigerant lines directly without bends.
!
Please note
Contamination (e.g. metal swarf) or moisture in
the copper pipes of the refrigerant lines will
cause the appliance to malfunction.
Point the pipe openings downwards or tempora-
rily plug them.
Note
■
The refrigerant lines of the indoor unit are charged
with nitrogen; positive pressure 2 bar (0.2 MPa).
■
If Euro flanged adaptors are used, braze the solder
connections using a shielding gas.
Installation sequence
Connecting the refrigerant lines
(cont.)
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...