10
Outdoor unit 230 V~
Type AWT/AWT-AC
221.A04
221.A05
221.A07
221.A10
221.A13
Compressor
Cable cross-section
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 4.0 mm
2
Max. cable length
29 m
25 m
25 m
20 m
20 m
or
or
Cable cross-section
—
—
—
3 x 4.0 mm
2
3 x 6.0 mm
2
Max. cable length
—
—
—
32 m
30 m
Outdoor unit 400 V~
Type AWT/AWT-AC
221.B10
221.B13
221.B16
Compressor
Cable cross-section
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
Max. cable length
30 m
30 m
30 m
Preparing for installation
Requirements for on-site connections
(cont.)
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...