Flare the pipe bends on their open end and secure
connection piece (twin connector) with union nuts.
Note
■
Flare the pipe end of the hot gas line by
approx. 0.5 mm.
■
Connection pieces must not be skewed. Check
the flared connections for firm seating.
2x
6.
Fig. 20
6. Type AWT/AWT-AC 221.A04
:
■
Slide the supplied union nuts (
⁷
⁄
₁₆
UNF for liquid
line,
¾
UNF for hot gas line) over the refrigerant
lines from the outdoor unit.
■
Flare the refrigerant lines from the outdoor unit.
■
Connect the supplied reducers with copper
sealing ring to the connection pieces (twin
connectors).
■
Secure the refrigerant lines from the outdoor unit
to the reducers using the union nuts.
Type AWT/AWT-AC 221.A05 to A13, 221.B10 to
B16
:
■
Slide the supplied union nuts (
⅝
UNF for liquid
line,
⅞
UNF for hot gas line) over the refrigerant
lines from the outdoor unit.
■
Flare the refrigerant lines from the outdoor unit.
■
Secure the refrigerant lines from the outdoor unit
to the connection pieces using the union nuts.
Tighten the nuts with the following torque:
Type AWT/AWT-AC
Line
Connection to the
indoor unit
Torque in Nm
221.A04
Liquid line
7
6 mm
⅝
UNF
with reducer
⅝
x
⁷
⁄
₁₆
14 to 18
Hot gas line
7
12 mm
⅞
UNF
with reducer
⅞
x
¾
50 to 62
221.A05
Liquid line
7
10 mm
⅝
UNF
33 to 42
Hot gas line
7
16 mm
⅞
UNF
63 to 77
Installation sequence
Connecting the refrigerant lines
(cont.)
5776 028 GB
Installation
Summary of Contents for AWT 221.A04
Page 77: ...77 Maintenance Checking the fuses cont 5776 028 GB Maintenance...
Page 87: ...87 Indoor unit parts lists Indoor unit hydraulics cont 5776 028 GB Components...
Page 90: ...90 Indoor unit parts lists Indoor unit cylinder cont 5776 028 GB Components...
Page 137: ...137 Wind direction 11 Wind loads 11 Keyword index Keyword index cont 5776 028 GB...
Page 138: ...138 5776 028 GB...
Page 139: ...139 5776 028 GB...