24
Problem
Cause
Solution
The charger is not
functioning
The AC input voltage or frequency
is out of range.
Ensure that the input voltage is
between 185 Vac and 265 Vac,
and that the frequency matches
the setting.
The thermal circuit breaker has
tripped.
Reset the 16 A thermal circuit
breaker.
The battery is not
being charged fully.
Incorrect charging current.
Set the charging current at
between 0.1 and 0.2x battery
capacity.
A defective battery connection.
Check the battery terminals.
The absorption voltage has been
set to an incorrect value.
Adjust the absorption voltage to
the correct value.
The float voltage has been set to
an incorrect value.
Adjust the float voltage to the
correct value.
The internal DC fuse is defective. Inverter is damaged.
The battery is
overcharged.
The absorption voltage has been
set to an incorrect value.
Adjust the absorption voltage to
the correct value.
The float voltage has been set to
an incorrect value.
Adjust the float voltage to the
correct value.
A defective battery.
Replace the battery.
The battery is too small.
Reduce the charging current or
use a battery with a higher
capacity.
The battery is too hot.
Connect a temperature sensor.
Battery charge
current drops to 0
when the absorption
voltage is reached
Alt. 1: Battery overtemperature
(> 50°C)
- Allow battery to cool down
- Place battery in a cool
environment
- Check for shorted cells
Alt 2: Battery temperature sensor
faulty
Unplug battery temperature
sensor from the MultiPlus.
Reset the MultiPlus by switching
it off, then wait for 4 seconds and
switch it on again
If the MultiPlus now charges
normally, the battery temperature
sensor is faulty and needs to be
replaced
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......