21
ds3-ds4: Setting charge voltages
ds3-ds4
Absorption
voltage
Float
voltage
Storage
Voltage
Absorption
Time
(hours)
Suitable for
dS3=off
dS4=off
(default)
14.4
28.8
57.6
13.8
27.6
55.2
13.2
26.4
52.8
8
Gel Victron Deep
Discharge
Gel Exide A200
AGM Victron Deep
Discharge
dS3=on
dS4=off
14.1
28.2
56.4
13.8
27.6
55.2
13.2
26.4
52.8
8
Gel Victron Long
Life (OPzV)
Gel Exide A600
(OPzV)
Gel MK battery
dS3=off
dS4=on
14.7
29.4
58.8
13.8
27.6
55.2
13.2
26.4
52.8
5
AGM Victron Deep
Discharge
Tubular plate or
OPzS batteries in
semi-float mode
AGM spiral cell
dS3=on
dS4=on
15.0
30.0
60.0
13.8
27.6
55.2
13.2
26.4
52.8
6
Tubular plate or
OPzS batteries in
cyclic mode
Batteries with high antimony content can typically be charged with a lower absorption
voltage than batteries with low antimony content. (Please refer to our book “Electricity on
Board” downloadable from our website www.victronenergy.com for details and suggestions
about charging batteries). Contact your battery supplier for the correct charge voltages and
change (with VE-configure) the voltage settings if required.
The default charge current setting is 75% of the maximum charge current. This current will be
too high for most applications.
For most battery types the optimal charge current is 0.1-0.2x the battery capacity.
ds5: Inverter frequency
off = 50Hz
on = 60Hz
ds6: Search Mode
off = off
on = on
ds7: AC input current limit
off = 12 Amp
on = 4 Amp
Store the settings by moving Dip switch 8 to “on” and back to “off”.
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......