17
5.5.1.5 Examples
examples of settings:
DS-8 AC input
on
DS-7 AC input
on
DS-6 AC input
on
DS-5 AES
off
DS-4 Ch. current
on
DS-3 Ch. current
off
DS-2 N/A
off
DS-1 N/A
off
DS-8
on
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
off
DS-7
on
DS-6
on
DS-5
off
DS-4
on
DS-3
on
DS-2
off
DS-1
off
DS-8
on
DS-7
on
DS-6
off
DS-5
on
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 1, Example 1 (factory
setting):
8, 7, 6 AC-in: 50 A*
5 AES: off
4, 3 Charging current: 75 %
2, 1 N/A
Step1, Example 2:
8, 7, 6 AC-in: 50 A*
5 AES: off
4, 3 Charge: 100 %
2, 1 N/A
Step1, Example 3:
8, 7, 6 AC-in: 16 A
5 AES: off
4, 3 Charge: 100 %
2, 1 N/A
Step1,Example 4:
8, 7, 6 AC-in: 30 A*
5 AES: on
4, 3 Charge: 50 %
2, 1 N/A
*Maximum is limited to 16 A in case of models with 16 A transfer switch
To store the settings after the DIP switches are set according to the required values: press the 'Up' button for 2 seconds (
upper
button
to the right of the DIP switches, see appendix A, position J).
The overload and low-battery LEDs will flash to indicate acceptance of
the settings.
We recommend making a note of the settings, and filing this information in a safe place.
The DIP switches can now be used to apply the remaining settings (step 2).
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (
L2
,
L3)
. These settings are imposed on the whole system by the leader
L1
. If a setting is irrelevant for
L2
,
L3
devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (
not relevant for L2, L3
)
ds8-ds7
Absorption
voltage
Float
voltage
Storage
voltage
Suitable for
off off
14.1
28.2
56.4
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV)
Gel MK battery
off on
14.4
28.8
57.6
13.8
27.6
55.2
13.2
26.4
52.8
Gel Victron Deep Discharge
Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate (OPzS)
on off
14.7
29.4
58.8
13.8
27.6
55.2
13.2
26.4
52.8
AGM Victron Deep Discharge
Tubular plate traction batteries in
semi-float mode
AGM spiral cell
on on
15.0
30.0
60.0
13.8
27.6
55.2
13.2
26.4
52.8
Tubular plate traction batteries or
OPzS batteries in cyclic mode
ds6: absorption time 8 or 4 hours (
na for L2, L3
)
on = 8 hours
off = 4 hours
ds5: adaptive charging algorithm (
na for L2, L3
)
on = active
off = inactive
(inactive = fixed absorption time)
ds4: dynamic current limiter
on = active
off = inactive
ds3: UPS function
on = active
off = inactive
ds2: converter voltage
on = 230 V
off = 240 V
ds1: converter frequency (
na for L2, L3
)
on = 50 Hz
off = 60 Hz
(the wide input frequency range (45-55 Hz) is 'on' by default)
Note:
-
If “adaptive charging algorithm” is on, ds6 sets the maximum absorption time to 8 hours or 4 hours.
-
If “adaptive charging algorithm” is off, the absorption time is set to 8 hours or 4 hours (fixed) by ds6.
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......