8
4. Installation
This product may only be installed by a qualified electrical engineer.
4.1 Location
The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at
least 10 cm around the appliance for cooling.
Excessively high ambient temperature will result in the following:
•
Reduced service life.
•
Reduced charging current.
•
Reduced peak capacity, or shutdown of the inverter.
Never position the appliance directly above the batteries.
The MultiPlus is suitable for wall mounting. For mounting purposes, a hook and two holes are provided at the back of the casing (see
appendix G). The device can be fitted either horizontally or vertically. For optimal cooling, vertical fitting is preferred.
The interior of the product must remain accessible after installation.
Try and keep the distance between the product and the battery to a minimum in order to minimize cable voltage losses.
For safety purposes, this product should be installed in a heat-resistant
environment. You should prevent the presence of e.g. chemicals, synthetic
components, curtains or other textiles, etc., in the immediate vicinity.
4.2 Connection of battery cables
In order to utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should
be used. See table.
12/3000/120
24/3000/70
48/3000/35
Recommended battery capacity (Ah)
400–1200
200–700
100–400
Recommended DC fuse
400 A
300 A
125 A
Recommended cross section (mm
2
)
per + and - connection terminal
0 – 5 m
2x 50 mm
2
50 mm
2
35 mm
2
5 – 10 m
2x 70 mm
2
2x 50 mm
2
2x 35 mm
2
* ‘2x’ means two positive and two negative cables.
Remark: Internal resistance is the important factor when working with low capacity batteries. Please consult your supplier or the relevant
sections of our book “Energy Unlimited”, downloadable from our website.
Procedure
Proceed as follows to connect the battery cables:
Use a torque wrench with insulated box spanner in order to avoid shorting the
battery.
Maximum torque: 11 Nm
Avoid shorting the battery cables.
•
Undo the four screws at the front of the enclosure and remove the front panel.
•
Connect the battery cables: see Appendix A.
•
Tighten the nuts well for minimal contact resistance.
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......