23
7. TROUBLE SHOOTING TABLE
Proceed as follows for quick detection of common faults.
DC loads must be disconnected from the batteries and the AC loads must be
disconnected from the inverter before the inverter and/ or battery charger is
tested.
Consult your Victron Energy dealer if the fault cannot be resolved.
Problem
Cause
Solution
The inverter fails
to operate when
switched on.
The battery voltage is too
high or too low.
Ensure that the battery
voltage is within the correct
value.
The inverter fails
to operate
Processor in no function-
mode.
Disconnect mains voltage.
Switch Front switch off,
wait 4 seconds
Switch front switch on.
The alarm LED
flashes.
Pre-alarm alt. 1. The DC
input voltage is low.
Charge the battery or
check the battery
connections.
The alarm LED
flashes
Pre-alarm alt. 2. The
ambient temperature is too
high.
Place the inverter in a cool
and well-ventilated room,
or reduce the load.
The alarm LED
flashes.
Pre-alarm alt. 3. The load
on the inverter is higher
than the nominal load.
Reduce the load.
The alarm LED
flashes.
Pre-alarm alt. 4. Voltage
ripple on the DC input
exceeds 1.25Vrms.
Check the battery cables
and terminals.
Check the battery capacity;
increase if necessary.
The alarm LED
flashes
intermittantly.
Pre-alarm alt. 5. Low
battery voltage and
excessive load.
Charge the batteries,
reduce the load or install
batteries with a higher
capacity. Use shorter
and/or thicker battery
cables.
The alarm LED is
on
The inverter did cut out
following a pre-alarm.
Check the table for the
appropriate course of
action.
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......