3. OPERATION
3.1 On/Off/Charger Only Switch
When switched to "on", the product is fully functional. The inverter will come into
operation and the LED "inverter on" will light up.
An AC voltage connected to the "AC in" terminal will be switched through to the "AC out"
terminal, if within specifications. The inverter will switch off, the "mains on" LED will light
up and the charger commences charging. The "bulk", "absorption" or "float" LEDs will light
up, depending on the charger mode.
If the voltage at the "AC-in" terminal is not within specifacations, the inverter will switch
on.
When the switch is switched to "charger only", only the battery charger of the MultiPlus
will operate (if mains voltage is present). In this mode input voltage also is switched
through to the "AC out" terminal.
NOTE: When only the charger function is required, ensure that the switch is switched to
"charger only". This prevents the inverter from being switched on if the mains voltage is
lost, thus preventing your batteries from running flat.
3.2 Remote control
Remote control is possible with a 3-way switch or with a Multi Control panel.
The Multi Control panel has a simple rotary knob with which the maximum current of the AC
input can be set: see PowerControl and PowerAssist in Section 2.
For the appropriate DIP switch settings, see sect. 5.5.1.
3.3 Equalisation and forced absorption
3.3.1 Equalisation
Traction batteries may require regular equalisation charging. In the equalisation mode, the
MultiPlus will charge with increased voltage for one hour (1V above the absorption voltage for
a 12V battery, 2V for a 24V battery). The charging current is then limited to 1/4 of the set
value. The “bulk” and “absorption” LEDs flash intermittently.
Equalisation mode supplies a higher charging voltage than most DC consuming
devices can cope with. These devices must be disconnected before additional
charging takes place.
3.3.2 Forced absorption
Under certain circumstances, it can be desirable to charge the battery for a fixed time at
absorption voltage level. In Forced Absorption mode, the MultiPlus will charge at the normal
absorption voltage level during the set maximum absorption time. The “absorption” LED will
be ‘on’.
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......