23
8. Technical specifications
MultiPlus
12/3000/120-16 230V
12/3000/120-50 230V
24/3000/70-16 230V
24/3000/70-50 230V
48/3000/35-16 230V
48/3000/35-50 230V
PowerControl / PowerAssist
Yes
AC input
Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz
Maximum feed through current (A)
16 / 50
Minimum AC supply current capacity
for PowerAssist (A)
2,3 / 5,3
INVERTER
Input voltage range (V DC)
9,5 – 17
19 – 33
38 – 66
Output
(1)
Output voltage: 230 VAC ± 2 % Frequency
:
50 Hz ± 0,1 %
Cont. output power at 25 °C / 77 °F (VA)
(3)
3000
3000
3000
Cont. output power at 25 °C / 77 °F (W)
2400
2400
2400
Cont. output power at 40 °C / 104 °F (W)
2200
2200
2200
Cont. output power at 65 °C / 150 °F (W)
1700
1700
1700
Peak power (W)
6000
6000
6000
Maximum efficiency (%)
93
94
95
Zero-load power (W)
20
20
25
Zero-load power in AES mode (W)
15
15
20
Zero-load power in Search mode (W)
8
10
12
CHARGER
AC Input
Input voltage range: 187-265 VAC Input frequency: 45 – 55 Hz
Power factor: 1
Charge voltage 'absorption' (V DC)
14,4
28,8
57,6
Charge voltage 'float' (V DC)
13,8
27,6
55,2
Storage mode (V DC)
13,2
26,4
52,8
Charge current house battery (A)
(4)
120
70
35
Charge current starter battery (A)
4 (12 V and 24 V models only)
Battery temperature sensor
Yes
GENERAL
Auxiliary output
Max. 16A Switches off when no external AC source available
Programmable relay
(5)
Yes
Protection
(2)
a - g
Common Characteristics
Operating temp.: -40 to +65 °C (-40 – 150 °F) (fan assisted cooling)
Humidity (non-condensing): max 95 %
ENCLOSURE
Common Characteristics
Material & Colour: aluminium (blue RAL 5012) Protection category: IP 20, pollution degree 2, OVC3
Battery-connection
M8 bolts (2 plus and 2 minus connections)
230 V AC-connections
Screw terminals 13 mm² (6 AWG)
Weight (kg)
19
Dimensions (hxwxd in mm)
362 x 258 x 218
STANDARDS
Safety
EN 60335-1, EN 60335-2-29, IEC62109-1
Emission / Immunity
EN 55014-1, EN 55014-2, EN 61000-3-3
Automotive Directive
2004/104/EC
1) Can be adjusted to 60 Hz; 120 V 60 Hz on request
Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230 VAC on inverter output
g. Input voltage ripple too high
3) Non linear load, crest factor 3:1
4) At 25 °C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start/stop function
AC rating: 230 V/4 A
DC rating: 4 A up to 35 VDC and 1 A upto 60 VDC
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......