18
WeakAC
Strong distortion of the input voltage can result in the charger hardly operating or not
operating at all. If WeakAC is set, the charger will also accept a strongly distorted voltage, at
the cost of greater distortion of the input current.
Recommendation: Turn WeakAC on if the charger is hardly charging or not charging at all
(which is quite rare!). Also turn on the dynamic current limiter simultaneously, and reduce the
maximum charging current to prevent overloading the generator if necessary.
Not adjustable with DIP switches.
BoostFactor
Change this setting only after consulting with Victron Energy or with an engineer trained by
Victron Energy!
Not adjustable with DIP switches.
Programmable relay
By default, the multi-functional relay is set as an alarm relay, i.e. the relay will de-energise in
the event of an alarm or a pre-alarm (inverter almost too hot, ripple on the input almost too
high, battery voltage almost too low).
Not adjustable with DIP switches.
Near the connection terminals an LED illuminates when the relay is activated (refer to S, see
appendix A).
Summary of Contents for MultiPlus Compact 12/1200/50-16
Page 2: ......
Page 29: ......
Page 30: ...www victronenergy com Appendix A overview connections ...
Page 31: ...Appendix A overview connections ...
Page 33: ...Appendix B installation information ...
Page 35: ...APPENDIX C parallel connection ...
Page 36: ...www victronenergy com APPENDIX D three phase connection ...
Page 39: ......
Page 40: ...www victronenergy com ...
Page 43: ......
Page 70: ...APPENDIX A Connection overview ...
Page 72: ...APPENDIX B Installation information ...
Page 74: ...APPENDIX C Parallel connection APPENDIX D Three phase connection ...
Page 77: ...www victronenergy com 255m 125m 520m 95mm ...
Page 78: ......
Page 79: ......
Page 82: ......
Page 106: ...24 ...
Page 121: ......
Page 122: ......
Page 123: ......