Specifications
Vertiv
|
Large System, 3-Phase UPS Battery System Installation Manual
59
Table 20
Liebert NXL
™
Junction Cabinet specifications
Battery Specifications
Value
500-750kVA
Attached
Stand-Alone
800-1100kVA
Attached
Nominal Battery Bus, VDC
480V
Battery Float Voltage, VDC
540V
Minimum EOD Voltage, VDC
384V (for VRLA / Flooded Lead Acid)
Physical Parameters
Width, in (mm)
15.5 (393)
30.9 (785)
17.5 (445)
Depth, in (mm)
33.5 (850)
33.5 (850)
33.5 (850)
Height, in (mm)
76.8 (1950)
76.8 (1950)
76.8 (1950)
Weight, lb (kg) approx.
255 (115)
400 (180)
255 (115)
Color
Black (ZP-7021)
Degree of Protection for UPS Enclosure
IP 20
Minimum clearance, Top
24" (610mm)
Minimum clearance, Back
0"
Minimum clearance, Sides
0"
Location of cable entrance
Top or Bottom
Standards and Conformities
UL 1778; CSA 22.2 107.3; FCC Part 15, Class A
ISTA Procedure 1H; WEEE; IBC 2012/CBC 2010
Environmental
Storage Temperature Range, °F (°C)
-13°F to 158°F (-25°C to 70°C)
Operating Temperature Range, °F (°C)
32°F to 104°F (0 to 40°C)
Relative Humidity
Maximum 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude above MSL, ft (m)
4920 (1500) (as per IEC 62040/3) -
1% maximum kW derate / 328ft rise between 4900-9800ft
(100m rise between 1500-3000m)
1.
Width dimensions are with side panels attached. Subtract 1.4" (35mm) for dimensions without side panels.
2.
Depth dimensions include the front door and rear panel.
Table 21
Alber
®
battery monitoring option specifications
Electrical Data
Value
Input Voltage
220-600VAC
Input Current
< 0.5A
Frequency
60Hz
Summary of Contents for Liebert NXL 1100
Page 2: ...Liebert Large System 3 Phase UPS Battery System Installation Manual...
Page 69: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 62 NOTES...
Page 70: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 63...
Page 71: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 64...