Installation Drawings
Vertiv
|
Large System, 3-Phase UPS Battery System Installation Manual
21
3.0 INSTALLATION DRAWINGS
Figure 18
Outline drawing, Liebert top-terminal, 47" (1194mm) wide battery cabinet
48.1" (1223mm)
33.4" (848mm)
33.9"
(848mm)
26.4"
(672mm)
16.5"
(418mm)
76.8"
(1950mm)
Center of
Gravity
Center of
Gravity
FRONT
RIGHT SIDE
ISOMETRIC VIEW
1. 24" (610mm) minimum clearance above the unit is required
for air exhaust.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry is available through removable
access plates.
4. All wiring must be in accorance with national and local
electrical codes.
5. Width dimension is without side panels; add 0.7" (18mm)
per side where applicable.
6. Depth dimension includes the front door and rear panel.
7. Refer to the battery technical information drawing for
more information.
BPP12003
Pg. 1, Rev. 0