Installation Drawings
Vertiv
|
Large System, 3-Phase UPS Battery System Installation Manual
27
Figure 24
Outline drawing, Liebert front-terminal battery cabinet
33.4" (848mm)
38"
(965mm)
37.8" (960mm)
Shipping Split
63" (1600mm)
15.7"
(399mm)
14"
(356mm)
12.2"
(311mm)
76.8"
(1950mm)
Center of
Gravity
Both Sections
FRONT
FRONT
RIGHT SIDE
Bottom
Cable Entry
ISOMETRIC VIEW
Shipping Split
Shipping Split
1. 24" (610mm) minimum clearance above the unit is required
for air exhaust.
2. Keep cabinet within 15 degrees of vertical.
3. Top and bottom cable entry is available through removable
access plates.
4. Control wiring and power wiring must be run in separate
conduit.
5. All wiring must be in accorance with national and local
electrical codes.
6. Width dimension is without side panels; add 0.7" (18mm)
per side where applicable.
7. Depth dimension includes the front door and rear panel.
8. Refer to the battery technical information drawing for
more information.
BPP12002
Pg. 1, Rev. 0
Summary of Contents for Liebert NXL 1100
Page 2: ...Liebert Large System 3 Phase UPS Battery System Installation Manual...
Page 69: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 62 NOTES...
Page 70: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 63...
Page 71: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 64...