![Vertiv Liebert NXL 1100 Installation Manual Download Page 61](http://html1.mh-extra.com/html/vertiv/liebert-nxl-1100/liebert-nxl-1100_installation-manual_1008262061.webp)
Installation Drawings
Vertiv
Large System, 3-Phase UPS Battery System Installation Manual
54
Figure 52
Alber
®
battery monitoring assembly diagram
Table 18
Alber battery monitoring assembly connections
Input
Voltage
Alber Transformer-2: Wht
Jumper
Alber Transformer-1: Blk
F4-F5 Fuse Rating
600
0 (Top)
300 (Top) to 0 (Bottom)
300 (Bottom)
1.25 A, 600VAC
480
0 (Top)
240 (Top) to 0 (Bottom)
240 (Bottom)
1.5 A, 600VAC
380
0 (Top)
300 (Top) to 208 (Bottom)
300 (Bottom)
2.0 A, 600VAC
208
0 (Top)
0 (Top) to 0 (Bottom) and
208 (Top) to 208 (Bottom)
208 (Top)
3.5A, 600VAC
BDS-3244-B2666
10
10
10
(6002-080)
24VAC
Power
Cable
11
12
1
11
Fiber Optic Cable
Fiber Optic Cable
Remote
Reset
Alarm
Contacts
13
AC Power
Cable
Alarm
Report
(2140-022)
Float
Current
Transducer
Discharge
Current
Transducer
String/Current
Transducer
Cable
Float
Current
Sensor
Ambient
Temperature
Sensor
9
9
4
5
3
8
BATTERY STRING
LOAD
CHARGER
or
Resistive load, voltage sense and
intertier sense connections to the battery
depend on the battery configuration
Red Dot
+
+
-
-
To UPS
Protected
120VAC
2
UXBM/50i BATTERY MODULE
J1
J2
J3
J4
J5
J6
This Monitor is designed for UPS
systems that are 700V or less and
a Maximum 350V with respect to
earth ground.
FIBER
OPTICS
TX
RX
FIBER
OPTICS
TX
RX
OUTPUT
1
(2140-036)
REMOTE
RESET
CRITICAL
RESET
MAINT.
RESET
HARDWARE
RESET
24VAC
Maximum
2 Strings
24VAC
Maximum
2 Strings
24VAC
Maximum
2 Strings
INPUT: 24VAC
600mA
24VAC
Maximum
2 Strings
OUTPUT
2
OUTPUT
3
OUTPUT
4
6
7
OUT
IN
UXCMi
UXCMi Controller
UXBM/50i Battery Module
Pre-wired sense/load leads
for cabinet applications
Sense/load leads
for open-rack applications
Ambient temperature leads
String/ripple current transducer
cable
String/ripple current transducers
Float current transducer cable
24VAC power cable
UXCMi AC power cable
Fiber optic cable
Float current transducer
UXCMi alarm connections
1
2
3
4
5
6
7
8
9
10
11
12
13
Summary of Contents for Liebert NXL 1100
Page 2: ...Liebert Large System 3 Phase UPS Battery System Installation Manual...
Page 69: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 62 NOTES...
Page 70: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 63...
Page 71: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 64...