![Vertiv Liebert NXL 1100 Installation Manual Download Page 36](http://html1.mh-extra.com/html/vertiv/liebert-nxl-1100/liebert-nxl-1100_installation-manual_1008262036.webp)
Installation Drawings
Vertiv
|
Large System, 3-Phase UPS Battery System Installation Manual
29
Figure 26
Terminal details, Liebert front-terminal battery cabinet
R0.28" x
0.75" Long
4.8" (122mm)
1.75" (44mm) Typical
1.75"
(44mm)
1.75"
(44mm)
1.75"
(44mm)
GROUND
BUSBAR
Ø0.56"
(14mm)
Positive
Terminal
Bus (+)
Negative
Terminal
Bus (-)
Access Plate
3.6" (91mm)
To Panel
1.7” (43mm)
To Panel
10.1"
(257mm)
To Panel
3.7" (95mm)
To Panel
0.9"
(23mm)
9.4"
(240mm)
21.2"
(538mm)
10"
(254mm)
Low-Voltage
Cable Entry
High-Voltage
Cable Entry
CONDUIT DETAIL A
Top Conduit Plate)
FRONT
FRONT
FRONT
CONDUIT DETAIL B
(Bottom Conduit Plate)
POSITIVE/NEGATIVE
BUS DETAIL
TOP VIEW
TOP VIEW
(Door Open)
RIGHT SIDE VIEW
Cable Entry
(See Detail B)
Bottom
Cable Entry
Cable Entry
(See Detail A)
57.6"
(1463mm)
NOTES
1. Top and bottom cable entry available
through removable access plates.
2. Control wiring and power wiring must be
run in separate conduit.
3. All wiring must be in accordance with
national and local electrical codes.
BPP12002
Pg. 3, Rev. 0
Summary of Contents for Liebert NXL 1100
Page 2: ...Liebert Large System 3 Phase UPS Battery System Installation Manual...
Page 69: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 62 NOTES...
Page 70: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 63...
Page 71: ...Specifications Vertiv Large System 3 Phase UPS Battery System Installation Manual 64...