Appendix
92VFD700 AC Drive Getting Started Guide
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P00.12
Power up
Keypad
reference
(P01.11)
0: 0.00Hz
1: The running
frequency of last
power-off
2: Preset 1
1
0
Run&Stop
000BH
P00.13
Motor1 rated
voltage
(P13.06)
0V
~
240V
0V
~
480V
0V
~
690V
1V
200V: 220V
400V: 380V
690V: 660V
Stop Only
000CH
P00.14
Motor1 rated
current
(P13.07)
G or P type:
0.1A
~
rated current
×
1.2
GP type:
0.1A
~
P type rated
current
0.1A
By model
Stop Only
000DH
P00.15
Motor1 rated
frequency
(P13.08)
1.00Hz
~
300.0Hz
0.01Hz
50.00Hz
Stop Only
000EH
P00.16
Motor1 rated
speed
(P13.10)
1rpm
~
60000rpm
1rpm
0rpm
Stop Only
000FH
P00.17
Auto-tune
(P13.02)
0: No action
1: Static Auto-tune1
2: Static Auto-tune2
3: Reserved
1
0
Stop Only
0010H
P00.18
Motor1 stator
resistance
(P13.11)
0.000Ω
~
60.000Ω
0.001Ω
0
Stop Only
0011H
P00.19
Motor1 Power
factor
(P13.05)
0.00
~
1.00
0.01
0.85
Stop Only
0012H