4 Parameters
VFD700 AC Drive Getting Started Guide 63
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.09 (P02.04)
Acceleration rate 1
0.0s
~
3600.0s
【
10.0
】
Run&Stop
P00.10 (P02.05)
Deceleration rate 1
0.0s
~
3600.0s
【
20.0
】
Run&Stop
Acceleration rate is the time from 0Hz to maximum reference.
Deceleration rate is the time from maximum reference to 0Hz.
For example:
P00.07 (P01.02) =100.00Hz, set up the maximum reference
P00.09 (P02.04) =10.0s
After starting, the drive output frequency will ramp from 0.00Hz to 50.00Hz and the
acceleration rate is:10.0s× (50.00Hz/100.00Hz) =5.0s
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.11 (P03.10)
Stop mode
0
~
3
【
0
】
Stop Only
0: Ramp stop
1: Coasting
2: Ramp stop +DC injection
3: CoDC injection
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.12 (P01.11)
Keypad power-up reference
0
~
2
【
0
】
Run&Stop
When the reference source is keypad, the reference when powered up is decided as below:
0: Starting reference is "0"
1: Starting reference is the output frequency before powered off
2: Starting reference is preset1 (P04.01)