4 Parameters
64VFD700 AC Drive Getting Started Guide
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.13 (P13.06)
Motor1 rated voltage
200V: 0V
~
240V
【
220V
】
400V: 0V
~
480V
【
380V
】
690V: 0V
~
690V
【
660V
】
Stop Only
P00.14 (P13.07)
Motor1 rated current
G or P type:
0.1A
~
rated current
×
1.2
GP type: 0.1A
~
P type rated
current
【
by model
】
Stop Only
P00.15 (P13.08)
Motor1 rated frequency
1.00Hz
~
300.0Hz
【
50.00
】
Stop Only
P00.16 (P13.10)
Motor1rated RPM
1rpm
~
60000rpm
【
0
】
Stop Only
P00.17 (P13.02)
Autotune selector
0
~
3
【
0
】
Stop Only
0: No action
1: Static autotune1 (first run)
When P00.17=1, press PRG to make sure the change and return to the ready stage, once there
is a run order, the drive will do the static auto-tune. When finished, P00.17=0, and the drive
will be in ready status.
2: Static autotune2 (every run)
When P0.17=2, every run order will be received, and the drive will do the autotune. After the
static autotune, the result will be saved into the EEPROM, and P0.17=2, and the drive will be
in running status.
3: Reserved
NOTE: If the auto-tune is working without load motor, the drive will trip at F016.
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.18 (P13.11)
Motor1 stator resistance
0.000
~
60.000Ω
【
0
】
Stop Only
After auto-tune finished, this parameter will be updated. If the resistance value is out of the
range, trip F016 will happen.
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.19 (P13.05)
Motor1power factor
0.00
~
1.00
【
0.85
】
Stop Only
PF and motor rated current (P00.14)are used to calculate the motor torquecurrent and
magnetizing current.
Parameter ID
Parameter Name
Range
【
Default
】
Change Mode
P00.20 (P13.01)
Motor voltage control mode
0
~
2
【
0
】
Stop Only
0: V/F control