Appendix
VFD700 AC Drive Getting Started Guide
127
Menu P12: Protection
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P12.01
Drive healthy
0: Off
1: On
1
Actual
Actual
04B0H
P12.02
Ramp hold by
high voltage
threshold
0: Off
1: On
1
1
Stop Only
04B1H
P12.03
high voltage
threshold
220V: 350V
~
370V
400V: 750V
~
780V
690V: 1000V
~
1125V
1
220V: 370V
400V: 780V
690V: 1125V
Stop Only
04B2H
P12.04
Pre-overload
alarm
0: Off
1: On
1
1
Stop Only
04B3H
P12.05
Pre-overload
threshold
80.0%
~
150.0%
0.1%
130.0%
Run&Stop
04B4H
P12.06
Pre-overload
delay time
0.0s
~
60.0s
0.1s
5.0s
Run&Stop
04B5H
P12.07
Auto reset
1
~
100
1
0
Stop Only
04B6H
P12.08
Auto reset
delay
2.0s
~
20.0s
0.1s
5.0
Stop Only
04B7H
P12.09
Input phase
loss delay
0.0s
~
3000.0s
0.1s
0.1s
Stop Only
04B8H
P12.10
Output phase
loss
0: Off
1: On
1
0
Stop Only
04B9H
P12.11
Motor
overload
protection
mode
0: Normal motor
1: Variable frequency
motor
1
1
Stop Only
04BAH
P12.12
Overload
factor
0
~
(drive rated
current/motor rated
current)
×
100%
1
100%
Run&Stop
04BBH