Appendix
VFD700 AC Drive Getting Started Guide 99
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P02.33 UP
/
DN reference
0: 0
1: Running
reference of last
power-off
2: 0, only can be
changed when
drive is active
3: Running
reference of last
power-off, only can
be changed when
drive is active
4: Preset 1, UP,
DOWN and reset
are active at all
times
5: Preset 1, UP,
DOWN are only
active when the
drive is running.
Reset is active at
all times.
1
0
Run&Stop
00E8H
P02.34
Power off UP
/
DN
output selector
0: Keep
1: Reset
1
0
Run&Stop
00E9H