Appendix
88VFD700 AC Drive Getting Started Guide
P03.27 and P03.28 provide a method of controlling the sequencer inputs and other functions
directly from a single control word. If P03.28 = 0, thecontrol word has no effect, if P03.28 = 1,
the control word is enabled. Each bit of the control word corresponds to a sequencing bit or
function as shown below,
A-table 1-7 Control word (P03.27) description
Bit
Function
0
Drive enable
1
Run
2
3-wire enable
3
Run forward
4
Run reverse
5
FWD/REV
6
Jog forward
7
Jog reverse
8
Fault reset
9
Saving parameters
10
Clean the trip tracking log
11
Enable comms. to write parameters
12
Reserved
13
Reserved
14
Reserved
15
Reserved
If P10.02 (drive address) = 0, the drive will not response to the master
.
A-table 1-8 Drive status (P10.14) description
Bit
Function
0
Drive has no fault
1
Drive is running
2
100% load
3
Frequency is arrived
4
Zero running
5
Running reverse
6
Current limit is working
7
Set time is up
8
Drive control order is changed to control terminal
9
Under voltage