Appendix
94VFD700 AC Drive Getting Started Guide
Menu P01: Reference
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P01.01
Reference
source
0: Keypad
1: UP/DOWN
2: Preset
3: AI1
4: AI2
5: Serial comms.
6: DI7 pulse
7: Optional card
8: User programmed
1
0
Run&Stop
0064H
P01.02
Maximum
frequency
0.00Hz
~
300.0Hz
0.01Hz
50.00
Hz
Stop Only
0065H
P01.03
Minimum
frequency
0.00Hz
~
Max. frequency
0.01Hz 0.00Hz
Stop Only
0066H
P01.04 Jog frequency 0.00Hz
~
P01.02
0.01Hz 5.00Hz
Run&Stop
0067H
P01.05
Skip
frequency1
0.00Hz
~
Max. frequency
0.01Hz 0.00Hz
Stop Only
0068H
P01.06
Skip
frequency2
0.00Hz
~
Max. frequency
0.01Hz 0.00Hz
Stop Only
0069H
P01.07
range of skip
frequency
0.00Hz
~
30.00Hz
0.01Hz 0.00Hz
Stop Only
006AH
P01.08 Reserved
−
−
−
−
−
P01.09
Keypad
reference
display
-
Max. frequency
~
+ Max. frequency
0.01Hz Actual
Actual
006CH
P01.10
UP/DOWN
reference
display
-
Max. frequency
~
+ Max. frequency
0.01Hz Actual
Actual
006DH