Appendix
112VFD700 AC Drive Getting Started Guide
Menu P07: Vector
ID
Function
Range
Step
Default
Change
Mode
Modbus
Register
Address
P07.01
Speed/Torque
mode change
condition
0: Only stop
1: Run&stop
1
0
Run&Stop
02BCH
P07.02
Speed/Torque
control
0: Speed
1: Torque
1
0
Run&Stop
02BDH
P07.03 Current limit
0.0%
~
300.0% (refer
to motor rated current)
0.1%
By
model
Run&Stop
02BEH
P07.04
~
P07.11
Reserved
−
−
−
−
−
P07.12
Current
controller Kp
gain
0.001
~
10.000
0.001
0.020
Run&Stop
02C7H
P07.13
Current
controller Ki
gain
0.00s
~
100.00s
0.01s
0.20s
Run&Stop
02C8H
P07.14
Current limit
protection
0: Enable current limit
protection
1: Disable current limit
protection above
fundamental frequency
2: Fast increase or
decrease current limit
protection disabled
3: Both disabled
1
0
Stop Only
02C9H
P07.15
Slip
compensation
error
0rpm
~
1500rpm
1rpm
0rpm
Run&Stop
02CAH
P07.16
Active current
limit
0.0%
~
300.0%
0.1%
200.0%
Run&Stop
02CBH