AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
102
The parameter value saved by the keyboard cannot be transmitted to the inverter when the inverter is
running or faulty or there is no parameter saved in the keyboard.
When the inverter parameter value is transmitted to the keyboard and saved, if the keyboard cannot be
copied after the keyboard is pulled out, the parameter copy operation needs to be performed again.
When the parameter value saved on the keyboard is transmitted to the inverter, if the keyboard is pulled
out, the previous part of the parameter modification will occur, and the latter part of the parameter is not
modified, and the operation needs to be performed again.
When the inverter parameter value is transmitted to the keyboard, the current running status of the
inverter will not be maintained. When the parameter value saved by the keyboard is transmitted to the
inverter, all the keys are invalid.
Error in the parameter copy The keyboard displays E.COP (parameter copy exception). At this time, the
copy is aborted and the parameter copy operation needs to be performed again. Press the PRG key to
exit the E.COP display and return to the monitoring.
When the software version is incompatible, it will prompt the error E.EDI, and the parameter value saved
by the keyboard cannot be transmitted to the inverter.
F04.06
Keyboard special function selection
Setting range: 0000
~
1111 Default:
0000
LED “0” digit: run command, stop/reset command
0: External priority, when the external is valid, the built-in is invalid.
1: Built-in priority, when the built-in is valid, the external is invalid
2: Both internal and external are valid, the stop/reset command takes precedence; when both forward and reverse
are active, the command is invalid.
LED “00” digit: keyboard communication options
0: Both internal and external keyboards are valid
1: Only the built-in keyboard is valid
2: Only external keyboard is valid
LED “000” digit: LCD Keyboard Language Selection
Set the LCD LCD keyboard display language, which is only effective when using the LCD LCD keyboard.
0: Chinese LCD LCD keyboard display content language is Chinese.
1: English LCD LCD keyboard display content language is English.
LED “0000” digit: Reserved
Used to select the function of REV/JOG key
0: REV
While keyboard control, press this button, inverter reverse run. Key REV/JOG not light.
1: JOG
While keyboard control, press this button, inverter JOG. Key REV/JOG light.
F04.07
Double-line keyboard REV/JOG selections
Setting range: 0-1
Factory set: 0
AC300 Series Vector Control Inverter Manual
Function Parameter Specifications
103
F04.08
STOP key function range
Setting range: 0~2
Factory set: 1
0: non keypad control is invalid
While under non keypad control mode,the stop key in the keypad can not be
used to stop.
1: non keypad control stop by stop mode
While under non keypad control mode,the stop key in the keypad can
be used as STOP key to stop.
It can be used as a stop button, and the stop mode is [F01.10] setting mode.
2: non keypad control free stop
While under non keypad control mode,the stop key in the keypad can be used
as STOP key to free stop.
It can be used as a stop button, the stop mode is free stop.
Note: While valid to terminal order or communication order, inverter is in stop lock state after press STOP key
under terminal control or RS485 control. If inverter needs to restart, stop oder needs to be given by selected
order channel to unlock stop state firstly.
F04.09
UP/DOWN key modification selections
Setting range: 0000-0212
Factory set: 0011
LED “0” digit: keyboard UN/DOWN key modify selection
0: Invalid UP/DOWN key can not modify parameters.
1: Modify frequency setting by key board numbers (F0.08) UP/DOWN key can modify parameters [F0.08].
2: Modify PID given setting by key board numbers (F11.01) UP/DOWN key can modify parameters [F11.01].
3: Used to adjust the [F04.10] setting parameter [Fxx.yy] The keyboard up and down keys can quickly modify the
setting value of the parameter [Fxx.yy].
LED “00” digit: keyboard UP/DOWN key store selection
0: No save after power down
1: Save after power down
It is used to select whether save the parameter modified by UP/DOWN key while power cut.
LED “000” digit: operation limit
0: Operation stop for adjusting
1: Adjusting only in operation, stop for holding
2: Adjusting in operation, stop for clearing
LED “0000” digit: reserved
F04.10
Keyboard up and down keys
to quickly modify the
parameter number setting
Custom shortcut modification
parameters
LED “00” digit: yy setting in Fxx.yy
LED “000” and “0000”digits: xx setting
in Fxx.yy
For example: "0008" means F00.08
For example: "0009" means F00.09
For example: "1101" means F11.01
Factory set: 0008
F04.11-
F04.13
Reserved