AC300 Series Vector Control Inverter Manual
Function Parameter Table
168
F10.17
Load pre alarm
detection setting
LED“0” digit: Detection
selection(protection 1)
0: Not detection
1: Detected load is too large
2: Detected load is too large only at
constant speed
3: Detected underloaded
4: Detected underloaded only at
constant speed
LED”00” digit: Alarm selection
0: alarm and continue operation
1: Fault protection and free stop
LED”000” digit: Detection
selection
(protection 2)
0: Not detection
1: Detected load is too large
2: Detected load is too large only at
constant speed
3: Detected underloaded
4: Detected underloaded only at
constant speed
0000
〇
0xA11
F10.18
Pre alarm detection
level 1 for load
0.0
~
200.0%
130.0%
〇
0xA12
F10.19
Load pre alarm
detection time 1
0.0
~
60.0s
5.0s
〇
0xA13
F10.20
Pre alarm detection
level 2 for load
.0
~
200.0%
30.0%
〇
0xA14
F10.21
Load pre alarm
detection time 2
0.0
~
60.0s
5.0s
〇
0xA15
F10.22
Reserved
0xA16
F10.23
Protection action of
speed bias excess
LED “0” digit: Detection selection
0: Not detected
1: Detected only at constant speed
2: Detecting
LED “00” digit: Alarm selection
0: Free stop and report fault
1: Alarm and continue operation
LED “000”/”0000” digit: Reserved
0000
〇
0xA17
F10.24
Detection threshold
when speed bias
0.0
~
60.0%
10.0%
〇
0xA18
F10.25
Detection time when
speed bias excess
0.0
~
60.0s
2.0s
〇
0xA19
AC300 Series Vector Control Inverter Manual
Function Parameter Table
169
F10.26
Stall protection action
LED “0” digit: Detection selection
0: Not detected
1: Detected at constant speed
2: Detecting
LED “00” digit: Alarm selection
0: Free stop and report fault
1: Alarm and continue operation
LED “000” digit: Reserved
LED “0000” digit: Reserved
0000
〇
0xA1A
F10.27
Stall detection
0.0
~
150.0%
110.0%
〇
0xA1B
F10.28
Stall detection time
0.000
~
2.000s
0.010s
〇
0xA1C
F10.29
Motor overshot
Protection threshold
0
~
200°C
〇
0xA1D
F10.30
Motor overshot Pre
alarm threshold
0
~
200°C
〇
0xA1E
F10.31-F
10.37
Reserved
F10.38
Malfunction
self-recovery times
0
~
5
0
〇
0xA26
F10.39
Malfunction
self-recovery interval
0.1
~
100.0s
1.0s
〇
0xA27
PID Process Control Parameter Group
NO.
Function description
Range of settings and definition
Factory
default
Feature
Address
F11.00
PID Controller given
signal source
0: Keypad digit PID
given
1: Reserved
2: AI1
3: AI2
4: Reserved
5: PUL
6: RS485
7: Option
card
8:Terminal
selection
0
●
0xB00
F11.01
Keyboard digit PID
given / feedback
0.00
~
100.0%
50.0%
●
0xB01
F11.02
PID given changing
0.00
~
60.00s
1.00s
●
0xB02
F11.03
PID controller
feedback signal
source
0: Keypad digital
PID feedback
1: Reserved
2: AI1
3:AI2
4: Reserved
5: PUL
6: RS485
7: Option
card
8:Terminal
selection
2
●
0xB03
F11.04
Feedback signal filter
0.000
~
6.000s
0.010s
●
0xB04
F11.05
Feedback signal gain
0.00
~
10.00
1.00
●
0xB05
F11.06
Given and feedback
0
~
100.0
100.0
●
0xB06